Nustian371
Member-
Posts
45 -
Joined
-
Last visited
-
Days Won
13
Nustian371 last won the day on October 10 2021
Nustian371 had the most liked content!
Profile Information
-
Gender
Male
-
Location
New Zealand
-
University
Nust, Bauhaus
-
Employer
Calibre Consulting
-
Interests
Structure Design
Recent Profile Visitors
The recent visitors block is disabled and is not being shown to other users.
Nustian371's Achievements
-
Nustian371 reacted to a post in a topic: Design of transfer beams
-
Nustian371 reacted to a post in a topic: Connection between wall and slab of ground floor
-
Nustian371 reacted to a post in a topic: Floating Column Design / Pick Up Column Design
-
SMAQ reacted to a post in a topic: Load Of External Precast Panels On Structural Frame
-
Load Of External Precast Panels On Structural Frame
Nustian371 replied to SMAQ's topic in Concrete Design
You can apply the as line load to your external beams or can add this onto the slab SDL load as well, either is fine. -
UmarMakhzumi reacted to a post in a topic: Steel Shed Modeling in SAP2000
-
You don't modify the steel stiffness in the software.
-
Nustian371 reacted to a post in a topic: Beam taking action of Column
-
UmarMakhzumi reacted to a post in a topic: Load transfer between confining element and brick masonry
-
UmarMakhzumi reacted to a post in a topic: Beam taking action of Column
-
UmarMakhzumi reacted to a post in a topic: Wind Load Application For "V" Shape BillBoard
-
SMAQ reacted to a post in a topic: Wind Load Application For "V" Shape BillBoard
-
so what are you expecting, in this case? the moment on the cantilever beam and column would be same.
-
hi i would have done it with pinned support in the model to get the net tension compression force at the base. i suspect your foundation size is not adequate ( just experience), as the framing you said above is 12mx5m = 60m2 *1.33= 79.8Kn *6= 473kn-m say the moment arm below 1.2m (foundation size) , 473/1.2= 394kN times your safety factor = 394*1.5 = 591 kN, if you go further and increase your moment arm still you got quite a force to resist the uplift. have a look at your foundation in each direction.
-
Hi What are your expectations, if the column have the load which needs to be transferred through the cantilever beam than what other load path would you expect?
-
Load transfer between confining element and brick masonry
Nustian371 replied to abbaskhan2294's topic in Concrete Design
I donot think i got your question properly, but what i understood is that can columns transfer the load to masonry walls supporting the beam above, the answer will be mixed, depending upon your construction type, for example in case of concrete/beam frame building the confinement of masonry is just transferring the loads of the masonry to column not the other way round, your beams and columns in this case are design elements, in case of a masonry house construction the design is based on load bearing walls so the loads transfer is mainly through the masonry walls. if you could do a quick free body sketch of your situation then maybe someone can answer much better. -
UmarMakhzumi reacted to a post in a topic: Water tank leakage
-
Its a very common steel tank design for water storage, waste water and fire water in industrial sites all around the world, not used much in Pakistan.
-
You havenot replied to earlier question of mine, anyways i see this very commonly on the concrete slabs with steel tanks of this size. we do the design and monitoring for such structures on weekly basis. I would recommend you using XYPEX concrete water proofing. This band can be applied outside the tank wall with the concrete. The crystallisation of the compound will stop the water leak. the second option you can use is to empty the tank and apply a band of SikaFlex carbodur sheets at the base of the tank, They will stop that as well.
-
UmarMakhzumi reacted to a post in a topic: confined masonry!!!
-
Muhammad Hashmi reacted to a post in a topic: Water tank leakage
-
Badar (BAZ) reacted to a post in a topic: Water tank leakage
-
You got quiet a few answers above, But i think the fundamental question is what is your tank design is it a steel liner tank with a additional liner layer inside for water proofing or is a pocket base, which i see in this case as the steel wall is embedded in the concrete. There are water seals around the tank wall in the pocket see examples of each below, that is the liner one You got that one. There is a waterseal as mentioned above if this seal is not isntalled carefully and if it gets broken or damaged somehow during site pore, the leak at the base can occur. Normally the concrete slab for such tanks have a very high requirement of crack control so i doubt that if thats not considered in design. I would recommend first check the design of the wall pocket (if the leak is there) and confirm with the site notes if the seal is provided. The remedial measures can only be suggested once the cause is known. There are several options which can be adopted.
-
I am not sure if i picked up your question, but normally the confining reinforcement at the ends of confined masonry is to transfer the loads in tension compression. The Confined masonry in an earthquake act as compression strut and there are equations and guidance in FEMA to work out the capacities of these diagonal strut members. We do these checks very commonly here in New Zealand for the seismic analysis of the existing confined masonry structures. I would recommend you to have a read of the document i am attaching. Its called C8 and its part of the documentation used for the detailed seismic analysis of structures here in New Zealand. Section_C8-Unreinforced_Masonry_Buildings.pdf
-
Nustian371 reacted to a post in a topic: Best University For MSc. Structural Engineering
-
Best University For MSc. Structural Engineering
Nustian371 replied to Engr. Arslan Raza's topic in Students Zone
Hi Arsalan, with all due respect, if you feel confident in what you are doing than no point of doing masters as this will just be a degree for you and waste of time/money, until unless you work with some competent engineers and challenge yourself with technical problems on bigger projects. There is nothing wrong in doing design work on your own, which you are doing but if you have never been to a design office or never sit with a senior engineer, I doubt your knowledge about the design codes and the application of different design clauses. I personal feel you should not be giving any structural advise (sorry but that is what i think). 2storeyplus buildings or small plazas may look simple but are very critical as they are the major building stock in pakistan, without prior design knowledge there are so many basic details which you learn only with a senior engineer or in a design office. I am pretty sure you are just copying the drawings for other consultant and engineers which is basically what contractor or builders do. There is no difference between what you are doing and what they are doing. You should keep your firm name as builders only as design part is doubtful. Apologies if something i said offends you but structural engineering is a profession which we as engineers pick and we do it passionately, there is no way of shortcuts. -
Unfortunately in Middle east i have experienced something similar, the person taking interview might not necessarily know all these answers as well but he will come up with these questions just to make sure that you know nothing and he knows everything, a bit unprofessional attitude, the questions should be as per the experience of the guy and the job description. I found out the reason for the interviews to be like that they prefer the reference alot rather going through interview process. Its just what i have seen definitely not same for all organisations.
-
I will agree with above and suggest you try to look for something in the UK market as this will be hugely beneficial for you professionally and the experience will be immense. the projects and there nature is different in UK market and u will be surprised with the approach methods for each design problem. This will provide you a good base and will help. I am sure you will land a job soon but keep your focus there only.
-
As explained above that metal deck have inbulit shear capacity for the shear flow in some cases and if the joists or beams below are designed for the simply supported cases than the metal deck is pretty much behaving like a scaffold. So it is possible but again check your design requirements and if they are complied than should be no issue.
-
Incase you model the wall for gravity only loads the modelling in the FEA analysis will still show you the hogging moments under certain load cases as it will take that as a deflection. You can try another simple approach in which you model the equivalent concrete beam element for the masonry above your beam slab similar to equivalent steel or concrete n=Es/Ec, This will provide the additional depth to the beam/slab below which will reduce the hogging moments. The issue i always found with the links and springs is the definition of there properties and the force capacity as it is very difficult to determine for the plastered walls or block masonry.