Jump to content

Ali Karami

Member
  • Posts

    4
  • Joined

  • Last visited

  • Days Won

    3

Ali Karami last won the day on March 13 2022

Ali Karami had the most liked content!

1 Follower

Profile Information

  • Gender
    Male
  • Location
    Tehran
  • University
    Tehran
  • Employer
    private

Ali Karami's Achievements

Newbie

Newbie (1/14)

6

Reputation

  1. i got it! but this can not be applied to "joint shear check for columns" of the top story. right?
  2. thank you! although i knew this (but not the reason behind) one can not find it in the ACI code and it is hard to imply this to ignorant people. any official written document for it?
  3. i want to know if it is mandatory to check 6/5 beam to column capacity control in the last floor of the building. because in the last floor, the joint only has one column and normally two beams and it is hard to satisfy this issue. you will need a bigger column (in size or reinforcing) compared to below floors. is there any exception for the last floor? (working with ACI)
×
×
  • Create New...

Important Information

By using this site, you agree to our Terms of Use and Guidelines.